- | | abstract=This function | + | | abstract=This function provides smoothing of an analog input. The function calculates the smoothing value by adding S/16 of previous value with (16-S)/16 of actual value. |
- | + | The formula used is:<br/> | |
Out = ([Smooth_factor]/16)[Prev_value]+((16-[Smooth_factor])/16)[Input_value]<br/> | Out = ([Smooth_factor]/16)[Prev_value]+((16-[Smooth_factor])/16)[Input_value]<br/> | ||
S = smoothing factor X1 = initial value/previous output X2 = new input from I/O table | S = smoothing factor X1 = initial value/previous output X2 = new input from I/O table | ||
Line 24: | Line 24: | ||
}} | }} | ||
- | |||
- | |||
- | |||
- | |||
- | |||
- | |||
- | |||
- | |||
- | |||
- | |||
- | |||
- | |||
- | |||
- |
Current revision as of 19:16, 18 September 2009
Analog Input Smoothing
contributed by: Simone Stefani
Link to File
Click here to view program file.
Abstract
This function provides smoothing of an analog input. The function calculates the smoothing value by adding S/16 of previous value with (16-S)/16 of actual value.
The formula used is:
Out = ([Smooth_factor]/16)[Prev_value]+((16-[Smooth_factor])/16)[Input_value]
S = smoothing factor X1 = initial value/previous output X2 = new input from I/O table
If you want to... | then enter... |
---|---|
Prevent the smoothing | 0 |
Provide minimal smoothing | 1 |
Provide maximum smoothing | 15 |
Disclaimer